Fuels | chemical waste, solid and liquid (source air) | |
Throughput of both lines | solid | 4.782 t/y |
liquid | 8.712 t/y | |
Butan | 1.095 t/y | |
Quellenabluft | 1.705 t(VOC)/y | |
Heat value | solid | 36 GJ/t |
Heat value | liquid | 30 … 40 GJ/t |
Flue gas volume flow | 32.000 Sm³/h dry | |
NOx uncleaned gas concentration | 200 … 1.000 mg/Sm³ dry | |
NOx cleaned gas concentration | < 80 mg/Sm³ dry | |
NOx convertion rate | > 85 % (guaranteed) | |
NH3 slip (end of boiler) | < 40 mg/Sm³ dry (guaranteed) | |
Reduction agent | ammoniacal water, 25% by weight | |
Reduction agent consumption | 900 t/y | |
Injection medium | changable low pressure steam or air | |
Injection medium consumption | 1.550 t/y (steam) each boiler | |
Boiler section | 3,3 m x 1,9 m | |
Number of injection levels | 1 | |
Number of injection lances | 2 | |
Type of lance | dual fluid injectionlance with rotary drive | |
Commissioning | December 1995 | |
Status 12/2019 | ||
Contact | Dr. Christoph Gottfried Leiter Energieversorgung +41 (0) 61 - 264 - 54 04 christoph.gottfried@getec-ip.ch | |
Link address | www.infrapark-baselland.com |