| Fuels | chemical waste, solid and liquid (source air) | |
| Throughput of both lines | solid | 4.782 t/y |
| liquid | 8.712 t/y | |
| Butan | 1.095 t/y | |
| Quellenabluft | 1.705 t(VOC)/y | |
| Heat value | solid | 36 GJ/t |
| Heat value | liquid | 30 … 40 GJ/t |
| Flue gas volume flow | 32.000 Sm³/h dry | |
| NOx uncleaned gas concentration | 200 … 1.000 mg/Sm³ dry | |
| NOx cleaned gas concentration | < 80 mg/Sm³ dry | |
| NOx convertion rate | > 85 % (guaranteed) | |
| NH3 slip (end of boiler) | < 40 mg/Sm³ dry (guaranteed) | |
| Reduction agent | ammoniacal water, 25% by weight | |
| Reduction agent consumption | 900 t/y | |
| Injection medium | changable low pressure steam or air | |
| Injection medium consumption | 1.550 t/y (steam) each boiler | |
| Boiler section | 3,3 m x 1,9 m | |
| Number of injection levels | 1 | |
| Number of injection lances | 2 | |
| Type of lance | dual fluid injectionlance with rotary drive | |
| Commissioning | December 1995 | |
| Status 12/2019 | ||
| Contact | Dr. Christoph Gottfried Leiter Energieversorgung +41 (0) 61 - 264 - 54 04 | |